Back to Company
Foundation Fieldbus Universal Bridge
Type:
Network Gateway
Description:
The DFI302 is a programable bridge able to integrate Modbus (RTU & TCP/IP), Foundation Fieldbus (H1 & HSE), HART and conventional I/O in one unit. It supports Function Block programing and can be configured as either a Modbus Client or Modbus Server.
Connectivity:
Modbus, Modbus TCP/IP
Features:
Integral part of SYSTEM302; single integrated unit of interface, linking device, bridge, controller, gateway, Fieldbus power supply and distributed I/O subsystem; tight integration with intelligent devices and software from multiple manufacturers due to use of open standards; Connects to existing equipment through conventional I/O and Modbus communication; Full redundancy and fault isolation for high safety and uninterrupted operation.
Specifications:
32-bit RISC; Sustained performance: 50 MIPS; Memory for code: 2 MB, 32-bit Flash memory (upgradable firmware);Memory for data: 2MB, 32-bit NVRAM; Fieldbus interface: 4 ports, independent with DMA; Physical layer standard: ISA-S50.02-1992; Baud rate: 31.25 kbps; MAU type: passive (not bus powered); Intrinsic safety: NOT compliant; Isolation: 500 Vac (each channel); Operating voltage/current ?5 V ?5 % / 1.0 A (typical); RJ-45 and RJ-12 connectors.
Copyright © 2005-2024 Modbus Organization, Inc. 800 Federal St., Andover, MA 01810. All rights reserved.